Reliable pressure measurement is essential for keeping industrial processes stable and controllable. In chemical plants, petroleum facilities, power stations and automated production lines, pressure transmitters convert changes in pressure into electrical signals that monitoring and control systems can interpret.
Among the different signal formats, the 4–20mA current loop remains a common choice for industrial instrumentation. Its practical advantages include dependable signal transmission over extended cable runs, compatibility with many PLC and DCS systems, and relatively strong resistance to electrical interference. However, choosing a transmitter requires more than confirming its output type. Engineers also need to evaluate the pressure range, supply voltage, loop resistance, housing material, electrical connection and environmental protection.
A stainless steel Pressure Transmitter can be considered for applications where mechanical durability and compatibility with the process medium are important. Understanding its operating principle and installation requirements helps reduce wiring errors and supports more reliable measurement.
1. Understanding the Operating Principle of a 4–20mA Pressure Transmitter
A pressure transmitter uses a sensing element to detect pressure changes and converts the measured value into a standardized electrical signal. In a 4–20mA system, the output current varies proportionally across the configured measurement range.
The lower range value corresponds to 4mA, while the upper range value corresponds to 20mA.
For example, consider a transmitter configured to measure pressure from 0 to 10 bar:
| Measured Pressure | Output Current |
|---|---|
| 0 bar | 4mA |
| 2.5 bar | 8mA |
| 5 bar | 12mA |
| 7.5 bar | 16mA |
| 10 bar | 20mA |
The output relationship can be described using the following formula:
Output Current = 4mA + [(Measured Pressure − Lower Range Value) / Measurement Span × 16mA]
The 4mA starting point is known as a live zero. This arrangement allows a control system to distinguish a normal zero-range measurement from certain electrical faults. For example, an open circuit may cause the current to fall to zero rather than remain at the normal 4mA lower-range value.
This feature makes the 4–20mA signal suitable for continuous pressure monitoring and industrial process control.
2. Why Industrial Systems Continue to Use 4–20mA Signals
Industrial environments often contain motors, pumps, variable-frequency drives and other electrical equipment. These devices can generate electromagnetic interference that affects measurement signals, particularly when sensors are installed far from the control cabinet.
A current-loop signal offers several practical benefits in these conditions.
Reliable transmission over long cable runs
A current signal is generally less sensitive to cable voltage drops than a voltage-based signal, provided the transmitter has sufficient operating voltage and the total loop load remains within its specified limits.
Resistance to electrical interference
Compared with low-level voltage signals, a properly installed current loop is generally less affected by induced electrical noise. This is useful in facilities with substantial electrical equipment.
Compatibility with industrial control systems
Many programmable logic controllers (PLCs), distributed control systems (DCSs) and data acquisition devices support 4–20mA analog inputs. This makes integration relatively straightforward when the input and transmitter configurations are compatible.
Live-zero fault indication
The 4mA lower-range signal provides a reference point above zero. A current reading outside the normal operating range can help maintenance personnel identify certain wiring or power-related problems.
These characteristics explain why 4–20mA remains widely used in petroleum processing, chemical manufacturing, power generation and other process industries.
3. Basic Wiring for a Two-Wire 4–20mA Transmitter
A common installation uses a two-wire, loop-powered configuration. The same pair of conductors supplies electrical power to the transmitter and carries the output current to the receiving instrument.
A typical series-connected circuit follows this arrangement:
-
DC power supply positive terminal connects to the transmitter positive terminal.
-
Transmitter negative terminal connects to the PLC analog input positive terminal.
-
PLC analog input negative terminal connects to the power supply negative terminal.
Before energizing the circuit, engineers should confirm the terminal markings, polarity and input configuration. The PLC channel must be configured to measure current rather than voltage.
A 24V DC supply is commonly used in industrial installations, but the permissible voltage depends on the selected transmitter model and the resistance of the complete loop. The wiring diagram provided by the manufacturer should always take priority over a general connection example.
For the product series discussed here, the specified power supply range is 9–30V DC. Intrinsically safe models require connection through an appropriate safety barrier. The exact model configuration and applicable installation requirements should therefore be checked before commissioning.
4. Calculating Loop Resistance and Power Supply Requirements
A 4–20mA transmitter needs enough available voltage to operate while driving the receiving instrument and the resistance of the connected wiring. If the total loop resistance is too high, the transmitter may be unable to maintain the required output current, particularly near the 20mA upper range.
For this product series, the maximum load resistance is expressed as:
Maximum Load Resistance ≤ (U − 15) / 0.02 Ω
In this formula, U represents the supply voltage in volts.
For a 24V DC supply, the calculation is:
Maximum Load Resistance ≤ (24 − 15) / 0.02 = 450Ω
This value represents the theoretical maximum under the stated formula. Actual installations must also account for cable resistance, PLC input resistance, safety barriers and any other components connected in series.
For example, a safety barrier or long cable may add resistance to the loop. Even if the transmitter and PLC are individually compatible, the complete circuit may exceed the permitted load.
Before commissioning, engineers should calculate the total loop resistance and verify that sufficient voltage remains available for the transmitter at the maximum output current.
5. Stainless Steel Housing and Ingress Protection
The transmitter housing protects internal sensing and electrical components from environmental exposure and mechanical damage. Material selection should take into account the process medium, installation conditions and maintenance requirements.
The listed housing material for this product range is stainless steel 1Cr18Ni9Ti. Stainless steel construction can be suitable for many industrial environments where mechanical strength and corrosion resistance are important. However, compatibility must still be assessed against the actual measured medium, sealing materials and sensor components.
The product specifications include IP65 and IP68 protection options.
IP65 indicates protection against dust ingress and water jets from any direction under the applicable test conditions. IP68 indicates dust-tight construction and protection against continuous immersion under conditions specified by the manufacturer.
An IP68 rating should not be interpreted as permission for unlimited underwater installation. Permitted immersion depth and duration depend on the manufacturer's specified test conditions. The cable entry, connector and assembled installation must also maintain the required protection level.
When evaluating a housing configuration, buyers should check:
-
Whether the measured liquid or gas is compatible with the wetted materials
-
Whether the installation is exposed to moisture, dust or outdoor conditions
-
Whether the pressure connection matches the process piping
-
Whether the selected cable outlet or connector provides suitable environmental protection
Selecting the protection rating according to actual site conditions is more useful than choosing a rating based on its numerical value alone.
6. Comparing Cable Outlet and Connector Configurations
Electrical connection design affects installation, maintenance and equipment replacement. Different industrial systems may require fixed cable connections or detachable connectors.
This product range provides three connection options: direct cable outlet, aviation connector and Hirschmann connector.
Direct cable outlet
A direct cable outlet is suitable for installations where a fixed wiring arrangement is preferred. It can reduce the number of separate connection interfaces, but cable routing, sealing and strain relief still need to be handled correctly.
Aviation connector
Aviation connectors provide a detachable interface. This can be useful when the transmitter needs to be disconnected for inspection, maintenance or replacement. Engineers should confirm the connector type, pin assignment and mating component before installation.
Hirschmann connector
Hirschmann connectors are used in industrial instrumentation and offer another option for installations requiring a compatible standardized connection. The corresponding plug and wiring arrangement must match the transmitter configuration.
Regardless of the connection method, installation personnel should verify polarity, pin assignments, cable specifications and the protection rating of the completed connection.
7. Common Questions About 4–20mA Pressure Transmitter Installation
Q1: Why does the transmitter output remain at 4mA?
A 4mA output may indicate that the measured pressure is at the configured lower range value. If the actual pressure is higher, check the pressure connection, measurement range, calibration and sensing condition. The signal loop should also be inspected.
Q2: What could cause the transmitter to produce no current output?
Possible causes include an incorrect supply voltage, reversed polarity, an open circuit, loose wiring or an incompatible receiving input. Check the power supply and circuit continuity before concluding that the transmitter is faulty.
Q3: Can a 4–20mA transmitter connect directly to a PLC?
Yes, if the PLC provides a compatible current input and the wiring follows the transmitter's requirements. It is important to determine whether the PLC input is active or passive and whether the circuit requires an external power supply.
Q4: Is a 24V DC power supply suitable?
The specified supply range for this product series is 9–30V DC, making 24V DC a typical option. However, the selected model, loop resistance and any required safety barrier must be considered before connection.
Q5: What happens when the loop resistance exceeds the permitted value?
Excessive resistance reduces the voltage available to the transmitter. This may result in inaccurate output or prevent the current from reaching 20mA. The total resistance of the cable, receiving input and other series components should be calculated during system design.
Q6: Can an IP68 transmitter operate underwater?
IP68-rated equipment is designed for immersion under specified conditions. The permitted depth and duration should be confirmed with the manufacturer. The cable entry and electrical connector must also maintain the required protection level.
8. Matching Pressure Range and Process Conditions
Choosing an appropriate pressure range is essential for measurement accuracy and safe operation. The listed measurement range for this product category extends from -100kPa through 0 to 10kPa and up to 100MPa, depending on the selected configuration.
The product supports gauge pressure measurement, including positive and negative gauge pressure. Its stated measured media include gases and liquids that are non-corrosive to the stainless steel, sealing materials and silicon components used in the sensor.
Other listed technical parameters include:
| Parameter | Specification |
|---|---|
| Measurement range | -100kPa through 0 to 10kPa, up to 100MPa depending on configuration |
| Pressure type | Positive and negative gauge pressure |
| Media | Compatible gases and liquids |
| Media temperature | -20°C to 85°C |
| Response time | 10ms |
| Pressure life | At least 5 million pressure cycles |
| Housing material | Stainless steel 1Cr18Ni9Ti |
| Power supply | 9–30V DC |
| Protection rating | IP65 / IP68 |
| Pressure connections | M20×1.5, G1/4, NPT1/2 or customized |
The pressure connection should be selected according to the process interface. A connection that does not match the piping or equipment can create installation difficulties and sealing problems.
Before ordering, engineers should confirm the required measurement range, pressure type, medium compatibility, operating temperature, electrical output and mechanical connection. These details help ensure that the selected configuration matches the actual process conditions.
9. Why Manufacturing Traceability Matters in Pressure Measurement
A transmitter's datasheet provides important information, but product consistency also depends on manufacturing processes, calibration, inspection and traceability. These factors become particularly relevant when sensors are used in demanding industrial environments or incorporated into larger measurement and control systems.
Danrui Sensor (Suzhou) Co., Ltd. focuses on the research, development and manufacturing of pressure and differential pressure measurement technologies. Founded in 2011, the company has been recognized as a National High-Tech Enterprise, a Private Technology Enterprise and a Technology-Based SME. It has also obtained ISO 9001 quality management, ISO 14001 environmental management and ISO 45001 occupational health and safety management system certifications.
The company holds nearly 20 patents related to CE-TUV explosion-proof and flameproof technologies and is a member of the China Instrument and Control Industry Association.
One important part of its manufacturing approach is the integration of an intelligent digital workshop with a Manufacturing Execution System (MES). Each sensor receives a unique serial number that connects records from assembly, testing and aging through to final inspection. This provides a traceable production workflow and supports standardized process management.
Danrui also operates a high-precision testing equipment platform, with some core equipment offering a maximum precision of 0.005%. The combination of testing equipment and digital production records provides a basis for monitoring manufacturing quality and tracking individual products.
Its measurement technologies serve industries including aerospace, shipbuilding, ordnance manufacturing and petrochemicals. The company also provides technical support and measurement and control solutions for industrial customers.
For buyers comparing Pressure Transmitter manufacturers, it is worth looking beyond the product's nominal range and output signal. Manufacturing records, inspection procedures, technical support and the ability to trace individual units are also relevant considerations when assessing a supplier.
Conclusion
A 4–20mA pressure transmitter is a practical measurement component for industrial monitoring and process control. Its effectiveness depends not only on the sensing element but also on correct loop wiring, adequate supply voltage, suitable load resistance and compatibility with the receiving control system.
Housing material, ingress protection and electrical connection options should be selected according to the installation environment. Pressure range, media compatibility, temperature limits and process connections also need to be confirmed before procurement.
The Pressure Transmitter range from Danrui Sensor (Suzhou) Co., Ltd. offers different measurement configurations, stainless steel housing options and electrical connection arrangements for industrial applications. By matching the technical specifications with actual operating conditions and evaluating the manufacturer's quality management practices, engineering teams can make a more informed selection for dependable pressure monitoring.